Main Technical Specification |
|
VOLTAGE RATINGS |
|
Rated voltage(Ur) |
kV |
12 |
|
Rated short-time(1min)power-frequency withstand voltage(Ud) |
kV |
48 |
|
Rated lightning impulse withstand voltage(Peak)(Up) |
kV |
85 |
|
Rated frequency(fr) |
Hz |
50 |
|
CURRENT RATINGS |
|
Rated current(Ir) |
A |
1250 |
|
Circuit resistance at lowest rated contact force |
μΩ |
≤30 |
|
Rated short-circuit breaking current(lsc) |
kA |
20/25 |
|
Breaking operations of rated short circuit breaking current |
Times |
30 |
|
Rated short-time withstand current(lk) |
kA |
20/25 |
|
Rated duration of short-circuit(tk) |
s |
4 |
|
Rated peak withstand current(lp) |
kA |
50/63 |
|
Rated short-circuit making current(lMc) |
kA |
50/63 |
|
Rated cable-charging breaking current(lc) |
A |
25 |
|
Rated breaking current of single capacitor bank(lsb) |
A |
400/630 |
|
Rated breaking current of back-to-back capacitor bank(lbb) |
A |
400 |
|
MECHANICAL DATA |
|
Weight of movable parts |
kg |
≤0.7 |
|
Closing force due to bellow and atmosphere |
N |
70±40 |
|
Force required to hold contacts open at full stroke |
N |
120±50 |
|
MECHANICAL REQUIREMENTS |
|
Clearance between open contacts |
mm |
9±1 |
|
Average opening speed (contact close position~75%contact gap) |
m/s |
12±0.3 |
|
Average closing speed (30%contact gap-contact close position) |
m/s |
0.8±0.2 |
|
Rated added external contact final force |
N |
2000±200 |
|
Added external contact force at contact touch point |
1400±100 |
|
Contact bouncing duration at closing operation |
ms |
≤2 |
|
Closing and opening non-simultaneity of three-phase contacts |
ms |
≤1 |
|
Maximum rebound during opening |
mm |
≤2 |
|
LIFE |
|
Storage life |
years |
20 |
|
Rated mechanical endurance |
Times |
10000 |
|
Contacts limit erosion |
mm |
3 |